| absolute |
as in absolute freezing point which is minus 273 degrees
Kelvin - the Kelvin temperature scale developed by Lord
Kelvin in the 1800's is also known as the absolute temperature
scale. It is a scale mainly used by scientists and the
zero point is considered the lowest temperature of anything
in the universe. 0ºK is equivalent to -273.16º Celsius.
|
| acrib |
acronym for air conditioning refrigeration industry board |
| air | we all
need it to breathe, sometimes it is dirty and polluted, sometimes it is clean
and fresh |
air conditioner | term
used to describe a packaged (complete) air conditioning unit in one box, as in
mobile, portable, window, console or rooftop |
|
air flow | as in volume air flow rate needed
to transfer heat |
| ammonia |
a very toxic, slightly flammable substance that can be used as a refrigerant. |
| anemometer | instrument
used to measure air velocity (speed) |
|
ari | a standard test condition but does not
relate to UK design conditions - see nominal duty |
biocide | used
in your drip tray to keep condensate trays and drains clean - also sometimes referred
to as tabs, Comfort use them for maintenance contract customers. |
| Btu | a
measurement of heat, the British thermal unit, as heat flow rate = Btu/hr. Put
simply, one Btu is the amount of heat required to raise the temperature of 1 lb.
of water 1 degree Fahrenheit. Heat flow rates are now measured in watts or kilowatts. |
| cassette |
a fan coil unit that fits mainly in the ceiling void with only a diffuser plate
visible, diffuses conditioned air in one, two, three or four directions |
| Celsius |
the correct metric unit of temperature measurement 0 degrees Celsius is freezing
point and 100 degrees Celsius is boiling point for water |
|
centigrade | see Celsius, it's effectively
the same |
| cfc |
a chlorofluorocarbon that is now not allowed to be used as a refrigerant, typically
R11 or R12 |
| cfm |
an imperial measurement of air flow rate - cubic feet per minute |
| chiller | a machine
that uses refrigeration to produce chilled water |
|
cibse | acronym for the chartered institute
of building services engineers - UK authority on design matters |
| close control |
commonly means air conditioning to precise control requirements of air temperature,
humidity and cleanliness - very expensive to own and run and wastes energy but
is sometimes necessary for machines, processes and historical archives or artefacts |
| comfort |
our namesake but what we all strive to achieve, air conditioning provides this
by altering the environment served |
|
comfort cooling | often derided by some engineers
(who should know better) as not being air conditioning, is a common term to describe
cooling for comfort as opposed to close control. Modern comfort air conditioning
systems control temperature very accurately but not humidity, as it would be an
unnecessary waste of energy to do so, purely for human comfort. |
| compressor |
at the heart of most air conditioning systems there has to be a refrigeration
compressor. With current technology without a compressor, there would not be enough
cooling for most applications |
|
condenser | a device used to condense a refrigerant
thereby rejecting the heat to another source, typically an air cooled or water
cooled condenser |
| condensing
unit | a machine comprising a compressor, condenser
and if air cooled, a fan, used to reject heat |
|
condensate | water, or the moisture removed
from the air when the air is cooled |
| conductivity |
the property or power of conducting heat. |
|
cooler | a machine, commonly using water,
a fan and a coil or mesh to provide evaporative cooling - very effective and cheap
to run in hot dry climates, but not so effective in humid climates, such as the
UK. It is now illegal to refer to them as air conditioners. |
| cooling | a
process of which there are many to remove either sensible or latent heat, or both,
which is then referred to as total heat |
|
cooling tower | a device, commonly used in
larger buildings to reject heat from a chiller to the atmosphere via water and
forced air. They have to be regularly cleaned and maintained, particularly to
prevent legionella bacteria forming within the water. It is probably preferable
to use air cooled condensers now. |
|
cop | the coefficient of performance, used
to determine how efficiently a heat pump operates. It is now common for modern
systems to exceed 3 to 1, whereby for every 1kw of electrical power used by the
unit 3kw of heat will be provided. Latest systems can exceed 4 to 1, but note
that the COP is related to external and internal temperatures. |
| dBA | a unit for measuring
sound power or pressure, deciBel on the A scale |
|
de-humidify | to remove moisture from the
air, achieved by mechanical cooling |
|
dew point | the temperature at which the moisture
in air condenses from a vapour back to a liquid. As in the condensation that forms
on a cold surface relative to air temperature, i.e. glazing or un-insulated ducts
or pipes. |
| diffusion |
the art or science of delivering air to achieve cooling or heating with good
air distribution without causing discomfort or draughts, uses a diffuser |
| diffuser |
a device forming part of an air conditioning unit or duct system to deliver
and diffuse air efficiently without causing discomfort or cold draughts |
| drip tray |
a component of most air conditioning units and fan coil units to collect the
condensate water removed from the air whilst cooling |
|
dry bulb | the dry air temperature - relative
to the wet bulb temperature - see wet bulb. |
dry
cooler | similar to a condenser |
| duct | a pipe
or tube made from various materials either rectangular, circular, oval, flexible,
vapour sealed or and insulated used to convey air. |
|
eer | energy efficiency ratio - a factor calculated
to determine how efficient a unit/system is. |
|
energy labelling | a system commonly used
from 2003 to show how energy efficient a unit or system is. |
| enthalpy | a
term used to determine the amount of moisture held by a specific volume of air
at a certain condition. |
evaporative
cooling | cooling effect caused by air blowing across
a moisture laden surface - see cooler - but also is the effect you feel if air
is blown across your skin. Try it now, you have moisture on your skin and by blowing
on it you will feel the cooling effect. |
|
evaporator | commonly the room unit of an
air conditioning unit, that gives off cooling by typically evaporating refrigerant
from a liquid to a gas. This action causes a refrigerated cooling effect and the
heat within the room air is transferred to the refrigerant. Also a component part
of a chiller. |
| fan |
a device used to move or circulate volumes of air |
|
fan coil | a device commonly having a fan
and a coil located within a room to provide local cooling or heating |
| Fahrenheit | the imperial
measurement of temperature |
| filter |
a device of varying types and qualities used to remove impurities from air,
gases or liquids. Always keep your filters clean! Dirty air conditioning filters
can be the largest cause of unnecessary breakdowns! |
freezing | the
process of converting a liquid or gas to a solid state |
|
gas | common term used to refer to some refrigerants,
which are at sometimes in a gaseous state - otherwise any substance that is freely
moving but is neither a solid or a liquid. |
|
grille | not to be confused with a diffuser,
a grille is device supplying or returning air, commonly a grille is never used
for supplying air from a ceiling, as it cannot diffuse the air. It should only
be used in a sidewall application or for vertical discharge. |
| gwp | global
warming potential - is a measurement of how much effect any given refrigerant
will have on global warming in relation to carbon dioxide. This is usually measured
over a 100 year period. The lower the value of GWP the better the refrigerant
is for the environment. |
| hc
| hydrocarbon, amongst other applications also
a highly flammable refrigerant - propane |
| hcfc |
hydrochlorofluorocarbon - a refrigerant, typically R22 - see refrigerants |
| heat pump |
a machine similar to a condensing unit but can reverse it's refrigeration cycle
and extract heat from an external source, air or water and then pump it back in
to a building to provide heating. Very efficient because even when it is -15ºC
outside there is still heat in the air and a heat pump can extract this heat,
upgrade it and use it. |
| hfc |
hydrofluorocaron - a refrigerant, typically R134A, R407C, R410A - see refrigerants |
| heat gain |
the heat a building or room gains causing possible discomfort, this can be
from many sources including solar gain (heat radiated from the sun), conduction
gain, (heat transmitted to a space due to the difference between the inside and
outside temperatures), lights, people, machines, fresh air etc. |
| heat loss |
The heat a building or room loses causing possible discomfort, this can be
primarily due to the difference between internal and external temperatures, but
also the amount of cold air used for ventilation. |
|
hi-wall | a term used to describe a room fan
coil unit mounted at high level on a wall |
|
humidistat | a control switch used to operate
(turn on and off) another device based on pre-set humidity conditions |
| humidity |
or relative humidity, the measurement of how much water vapour is contained
within the air - i.e. 50% is considered acceptable comfort, 20% would be an uncomfortable
dry condition and 100% means it's probably raining! |
|
hvca | acronym for the heating and ventilating
contractors association |
| hygrometer |
an instrument used to measure the relative humidity |
|
ice | solid water at 0ºC, -32ºF |
| internal heat gain | the
heat produced by internal rather than external sources, can be people, lights,
machines, computers, electronics, cooking, TV's, hot meals, etc. |
| inverter |
an electrical device that allows the frequency of the electric supply to be
varied from it's standard 50Hz, thereby allowing motors (compressors) to be run
at variable speeds. This in turn allows more precise delivery of energy to match
the required load at any one time, rather than a constant delivery, which may
not match. The result is an extremely controllable and energy efficient system
that is not only cheaper to run but also needs a smaller power supply. |
| Kelvin | see absolute |
| kcal | a measurement
of heat used in continental Europe, as 1000 calories - yes it's the same unit
those diet people keep referring to. |
|
kw | standard measurement of heat or power,
1kw = 1000 watts = 3412Btu/hr = 860kcal |
| kilowatt |
same as kw above |
| Kyoto |
protocol - we suggest you research this on the Internet, it covers the recommendations
to reduce global warming and is a very complex subject. Air conditioning manufacturers
and refrigerant producers are working hard to produce new and energy efficient
products. Make sure you read it all though, don't believe everything you hear
on the news or read. |
| joule |
a measurement of energy |
| latent
heat | the heat that does not change the temperature
but does change the state of a substance when added to or removed from it. |
| liquid | a substance
that is neither solid nor a gas |
|
low ambient | term used to refer to a low
external temperature, often an air conditioner or system will require low ambient
controls to enable it to keep on cooling with low external temperatures |
| legionella |
it's full name is Legionnaires' Disease (Legionellosis) and is a very uncommon
form of pneumonia caused by a bacterium that when inhaled may have serious consequences.
It is only possible to catch this via a water based aerosol and apart from natural
sources the most likely way a single individual can catch this is from a little
used shower head. Cooling towers that have not been correctly maintained more
often causes larger public outbreaks. |
|
mobile | as in a mobile air conditioner, you
simply wheel it in, plug it in and turn it on, firstly having decided where you
will put the condenser or how to discharge the flexible hose to external air.
You can also have a split mobile where the room unit is connected by an umbilical
to an external condenser. |
| monobloc |
term used to describe a single packaged mobile or portable air conditioner,
it will be a one piece unit normally with a flexible discharge hose, not a remote
condenser. |
| Montreal
| protocol covers the subject of substances
that deplete the ozone layer. |
|
mouth organ | slang term used to describe
a horizontal ceiling suspend room fan coil unit, now you know why, it is similar
to a mouth organ having slots on both sides through which air is blown. They normally
do not make music or any noise if properly designed. |
|
m3/hr | a measurement of air volume flow rate
- cubic metres per hour |
| m3/s |
a measurement of air volume flow rate - cubic metres per second |
| m/s | a measurement
of air velocity or speed - metres per second |
|
multi-split | a term used to describe a system
where there is one outdoor unit connected to a number of room fan coil units |
| nitrogen |
a constituent part of air - oxygen free nitrogen (OFN) an inert and safe gas
is used to pressure test refrigeration pipework and is passed through the pipework
when it is being installed. But only reputable companies do this. |
| nominal duty |
the standard means of measuring the capacity of an air conditioner or unit,
system etc., relates to conditions which mean nothing to UK |
| odp | ozone
depleting potential - new refrigerants have zero odp and therefore, if released
do not deplete the ozone layer. However, they still must not be released to atmosphere. |
| ofn | oxygen
free nitrogen - used in brazing copper refrigeration pipes to prevent moisture
and oxides collecting and remaining in the pipework during manufacture or on site
installation. Failure to use it can have disastrous effects later, causing expensive
failure of compressors. |
| oil |
used to lubricate the compressor, can be mineral oil, but increasingly synthetic
with new refrigerants |
| oxygen |
we need it to oxygenate our bloodstream and live, therefore we have to ensure
there is enough in the air we breathe. |
|
ozone | as in that layer above earth that
protects us from ultraviolet rays and other nasty things happening to our world.
Some refrigerants are ozone depleting, which if they were released could possibly
damage the ozone layer. New refrigerants are not able to deplete ozone. |
| physchrometrics |
the art or science of the relationships between air, gas, liquids used to calculate
air conditioning requirements |
| portable |
as for mobile air conditioner |
|
propane | or R290, although a naturally occurring
substance that can be used as a refrigerant it is also a highly flammable gas
and must be carefully used. |
| pressure |
the changing pressure of a substance can affect it's state and hence properties.
A compressor is used to change the pressure of a refrigerant and hence it's ability
to absorb or transfer heat. The pressure a compressor, fan or pump is capable
of producing will also affect how far a gas or liquid can be moved. The resistance
to pressure a pipe or duct causes will also determine how far a gas or liquid
can be moved. |
| R22 |
an hcfc refrigerant which from 2002 can only be installed new as small heat
pumps |
| R407C |
an hfc refrigerant that is non-ozone depleting, zero odp, commonly used in
small air conditioning systems |
|
R410A | an hfc blended refrigerant that is
non-ozone depleting, zero odp, but operates at higher pressures than other hfc
refrigerants. |
| R417A |
the zero odp replacement, suitable for new equipment and as a drop-in replacement
for existing R22 systems. |
|
refcom | the register of companies
assessed as competent to handle refrigerants |
refrigerant | a
substance used to absorb and transfer heat, can be air, water, gas or chemical. |
| refrigeration | the
process of mechanical cooling |
|
remote controller | a device that allows the
remote operation or setting of another device, can be "wireless" as
infrared or "hard wired" with a cable connecting - allows you to control
your air conditioning |
| sensible
heat | the heat which affects the temperature of
a substance. e.g. there is no moisture change, such as heat from machines, lights
or the sun etc. |
| sick building
syndrome | often blamed on air conditioning, but
is primarily due to insufficient or poor ventilation and also the chemicals used
in manufacture of furniture, carpets and other office equipment or processes |
| sling physchrometer |
looks like a football rattle (remember those!) but comprises two thermometers,
one to measure dry bulb, the other wet bulb temperatures. has to whirled around
to get air temperature and a correlation between the two temperatures gives us
the relative humidity |
| solar gain |
the heat gained by a building or room from the suns heat radiation. |
| sound | most
air conditioning systems are relatively quiet and do not cause noise disturbance
to users or the environment. It is common to illustrate equipment sound levels
as either sound power, or sound pressure in dBA (deciBel on the A scale). This
can be very confusing and the resultant room noise level is relative to many other
factors, resulting in a room noise level, often expressed as a NR or NC level. |
| split system |
an air conditioner that has been split, very common and ideal for most buildings,
the room unit or evaporator, fan coil is split (separated) from the condensing
unit, external or heat pump and connected by means of small bore pipes and cables. |
| tabs | see biocide |
| temperature |
a measurement of how hot or cold a substance is. A comfortable summer internal
temperature would be 24ºC, in Winter 21ºC |
|
thermometer | an instrument for measuring
the temperature |
| thermostat
| a device for controlling or switching on or off
another device based on a pre-set temperature. |
|
ton | an imperial measurement of refrigeration
heat - 1 ton = 12000Btu/hr or 3.517kw |
| total
heat | the sum total of sensible and latent heat |
| u value |
a calculated value used to further calculate the rate of heat flow through
a structure, e.g. the heat conducted through a wall, roof or window |
| vav | variable air volume
- a type of a/c system sometimes used in very large buildings |
| velocity | speed |
| vrf | variable
refrigerant flow - a common type of air conditioning used in many buildings today,
same as vrv - |
vrv | variable
refrigerant volume, a protected trademark for the system developed by Daikin and
now copied by many others who have to refer to it as vrf |
|
vwt | variable water temperature, a water
pipe loop system having both boilers to raise the temperature and dry coolers
or cooling towers to lower the temperature, small heat pumps are commonly connected
to the loop to either reject local heat to or extract heat from the loop. |
| vvt | variable
volume and temperature - a small ducted air system that can vary both the volume
of air and temperature to achieve either heating or cooling matched to the required
capacity |
| water |
we drink it, swim in it, pollute it and sometimes use it for air conditioning |
| water cooled |
heat rejected from a building is transferred to water. Not advisable if you
intend to use a cooling tower, unless you regularly maintain the system and ensure
water treatment is maintained but can be very efficient if using ground water
in conjunction with a heat pump, inverters and a vrf system |
| wet bulb | the
air temperature measured with a wet bulb - a small fabric sleeve around the bulb
of a thermometer and wetted |
| x
factor | many x factors are used to calculate such
things as the suns altitude, azimuth and angle of incidence to work out solar
gains on buildings. |
| y factor |
used with x factors as above. |
| z factor |
if you have read the whole of this document you deserve to get some zzzzzzzzz! |